抄録
<p>Electric cables play important roles for supplying power and for transmitting information and control signals. Therefore, their degradation may cause a serious problem. Silicone rubber (SiR) is widely used for electrical insulation in safety-related cables in nuclear power plants. In this paper, the ability of locating a degraded portion in a duplex cable insulated with SiR was compared between a system based on frequency domain reflectometry (FDR) being developed by the authors and a commercially available system called line resonance analysis (LIRA). Reflecting the fact that the FDR system can expand the measurement frequency range, FDR shows a higher sensitivity and a better resolution than LIRA. However, both methods cannot detect the degradation of SiR before its further use becomes uncommendable.</p>