Study on Voltage Fluctuation due to Ferranti Effect and Reverse Power Flow in High Voltage Distribution Line

Bibliographic Information

Other Title
  • 高圧配電線路におけるフェランチ効果と逆潮流による電圧変動に関する研究
  • コウアツ ハイデン センロ ニ オケル フ ェ ランチ コウカ ト ギャクチョウ ナガ ニ ヨ ル デンアツ ヘンドウ ニ カン ス ル ケンキュウ

Search this article

Description

In this paper, we investigated the relationship between static condenser installation and the characteristic of voltage variation due to Ferranti effect in high voltage distribution system incorporating with PV system. We investigated about the suppression of the Ferranti effect by detaching the static condenser capacitors. Focusing on the change in system voltage due to the Ferranti effect, we simulated the voltage change in the presence or absence of the static condenser capacitors. In simulation result, the highest voltage reduction occurred when the static condenser capacitor at the node number 24 was removed. However, the reduction of voltage rise is small as if only one static condenser is removed. Therefore, in order to control the system voltage by suppressing the Ferranti effect, it is necessary to release plenty of phase advance capacitors.

Journal

Details 詳細情報について

Report a problem