- The Effects of Frame and Inlet Sizes of Electronic Casing-Mounted Cooling Fans on Their P-Q Characteristics
- クウレイ ファン ノ P Q トクセイ ニ カンスル キョウタイ スンポウ オヨビ イリグチ スンポウ ノ エイキョウ
この論文をさがす
説明
This paper describes the effects of frame and inlet sizes of an electronic casing on the cooling fan performance. The performance of air-cooling fans is defined by their P-Q characteristics. Recent studies report that P-Q curves of cooling fans depend considerably on their operational environments. It is impossible for accurate CFD (Computational Fluid Dynamics) analyses to be performed on the thermal design of electronic equipments, including fans. In this study, we measured a fan performance in some frames and explored effects of environment for their P-Q characteristics, especially effects from area of frame and cooling air inlet sizes. From experimental results, it was found that the fan P-Q characteristics, especially flow rate were affected strongly by inlet sizes.
収録刊行物
-
- 日本伝熱学会論文集
-
日本伝熱学会論文集 16 (4), 147-156, 2008
社団法人 日本伝熱学会