低圧損化した移動層型デシカント空調の除湿特性

書誌事項

タイトル別名
  • Performance of Desiccant Air Conditioning Moving Bed with Lowered Pressure Drop
  • テイアツ ソンカ シタ イドウソウガタ デシカント クウチョウ ノ ジョシツトクセイ

この論文をさがす

抄録

A new desiccant air conditioning system, MCMB : Mesh partitioned Countercurrent Moving Bed, is proposed to achieve an efficient dehumidification at low pressure drop. The dehumidifying section is divided into two flow channels by a wire mesh. Air is introduced from the bottom of one of the channels, while desiccant particles are flowed down in the other channel at a slow speed to achieve updraft type moving bed. Length of the acrylic dehumidifying section is 600 mm with a rectangular cross-section of 50 mm by 5 mm for air flow channel and 50 mm by 10 mm for particle flow channel. Axial distribution of air temperature, Tg, relative humidity, φ, and particle temperature, Tp, are measured and dehumidification rate is obtained. Based on these results, it is found that the MCMB actualizes the efficient isothermal dehumidification at low pressure drop. Furthermore, the wire mesh governs the mass transfer step when the particles have higher adsorption rates such as Zeolite.

収録刊行物

  • 粉体工学会誌

    粉体工学会誌 50 (3), 212-218, 2013

    一般社団法人 粉体工学会

参考文献 (21)*注記

もっと見る

詳細情報 詳細情報について

問題の指摘

ページトップへ