オゾン層保護のための代替フロン採用におけるキャピラリチューブ閉塞

書誌事項

タイトル別名
  • Blockage of the Capillary Tube with the Alternative Refrigerant Adopted for Ozone Layer Preservation
  • オゾンソウ ホゴ ノ タメ ノ ダイタイ フロン サイヨウ ニ オケル キャピラリチューブ ヘイソク

この論文をさがす

抄録

When the refrigerant for refrigerator was switched from CFC12 to HFC134a for the preservation of the ozone layer, the refrigerant oil also had to be changed from mineral oil to ester oil for securing miscibility. Ensuring efficiency and lubricity has surely and steadily advanced but a trouble of capillary tube clogging has occurred. The blockage of a capillary tube is identified to have been caused by the mold lubricant of the plastic components adopted inside the compressor, which led the sludge accumulation mechanism to elucidation. On the basis of this outcome it came to be possible to prevent the blockage of capillary tube perfectly.

収録刊行物

  • ターボ機械

    ターボ機械 34 (11), 683-688, 2006

    一般社団法人 ターボ機械協会

参考文献 (8)*注記

もっと見る