Locating Partial Discharge Source Occurring on Distribution Line by Using FDTD and TDOA Methods

  • Tian Ye
    Dept. of Electrical and Electronic Engineering, Graduate School of Advanced Technology and Science, The University of Tokushima
  • Kawada Masatake
    Institute of Technology and Science, The University of Tokushima
  • Isaka Katsuo
    Institute of Technology and Science, The University of Tokushima

この論文をさがす

説明

In this paper, the finite difference time domain (FDTD) method is used to simulate the propagation of electromagnetic (EM) waves emitted from partial discharge (PD) occurred on distribution line. The simulation model is composed of the distribution line, a building, the ground, and four antennas mounted on a vehicle. Three pairs of time difference of arrival (TDOA) among antennas are used to locate PD position in three dimensions. The TDOAs are obtained by using standard cross-correlation (SCC) method. The superimposed positioning optimization on the time delay of arrival (SPOT) method is used to improve the location result.

収録刊行物

被引用文献 (2)*注記

もっと見る

参考文献 (21)*注記

もっと見る

詳細情報 詳細情報について

問題の指摘

ページトップへ