書誌事項
- タイトル別名
-
- Basic Study on Frequency Accelerated Aging Test for Joint Section of XLPE Cable
この論文をさがす
説明
We studied usefulness of a frequency accelerated aging test by paying attention to the number of partial discharge (PD) pulses and the accumulated PD charges per a cycle of frequency of applied voltage. The results shows that a frequency accelerated aging test is useful when the accumulated PD charges per a cycle of frequency of applied voltage with higher than PD inception voltage are the almost same as that at a commercial frequency of 60 Hz. If applied frequency is 1 kHz, an accelerated aging test with 16.6 times faster than that for 60 Hz can be achieved.
収録刊行物
-
- 電気学会論文誌. A
-
電気学会論文誌. A 136 (3), 155-156, 2016
一般社団法人 電気学会
- Tweet
詳細情報 詳細情報について
-
- CRID
- 1390001204598220288
-
- NII論文ID
- 130005132233
-
- ISSN
- 13475533
- 03854205
-
- 本文言語コード
- ja
-
- データソース種別
-
- JaLC
- Crossref
- CiNii Articles
- OpenAIRE
-
- 抄録ライセンスフラグ
- 使用不可