書誌事項
- タイトル別名
-
- Inspection of the Switching Surge for the Digital-Control-Panel Adjacent to 500kV GIS
- ディジタル セイギョバン ノ 500kV GIS キンボウ セッチ ニ オケル サージ ケンショウ
この論文をさがす
説明
Recently digital control panels have been installed for various controls adjacent to GIS. As the distance between the digital control panels and GIS is short, switching surge is transmitted without attenuation. Therefore we developed the digital control panel that implemented surge countermeasure. We verified that the digital control panel adjacent to 500kV GIS did not malfunction for switching surge. Moreover we measured the switching surge at the digital control panel and analyzed the intrusion route of switching surge by EMTP. As a result, we observed that the maximum voltages at a secondary circuit of CT and the maximum voltages at a secondary circuit of VT were 2.4kVp-p and 2.8kVp-p, respectively. The major frequencies of those voltage waveform were distributed almost more than 10MHz. In the EMTP, the intrusion route from the GIS to the secondary circuit of VT was calculated. The voltage waveforms at VT terminal calculated by EMTP agree with measured results in the view point of amplitude, frequency and damping time.
収録刊行物
-
- 電気学会論文誌B(電力・エネルギー部門誌)
-
電気学会論文誌B(電力・エネルギー部門誌) 130 (1), 84-90, 2010
一般社団法人 電気学会