乾式架橋・三層同時押出(E-E方式)の6.6kV撤去CVケーブルの水トリー劣化調査

DOI DOI Web Site Web Site Web Site ほか1件をすべて表示 一部だけ表示 参考文献16件

書誌事項

タイトル別名
  • Investigation of Water Tree Degradation in Dry-cured and Extruded Three-layer (E-E Type) 6.6kV Removed XLPE Cables
  • カンシキ カケハシ ・ サンソウ ドウジ オシダシ(E-E ホウシキ)ノ 6.6kV テッキョ CV ケーブル ノ ミズ トリー レッカ チョウサ
  • Investigation of Water Tree Degradation in Dry‐Cured and Extruded Three‐Layer (E‐E Type) 6.6‐kV Removed XLPE Cables

この論文をさがす

説明

Dry-cured and extruded three-layer (E-E type) 6.6kV cross-linked polyethylene (XLPE) cables were introduced into electric power systems more than 30 years ago, but they do not experience failures because of water tree degradation. Also, the degradation index of water treeing for these cables has not been established. Therefore, investigating results of residual breakdown voltage and water tree degradation of these cables will help us plan for cable replacement and determine water tree degradation diagnosis scheduling, and will be fundamental data for cable lifetime evaluation. In this study, the authors measured the AC breakdown voltages of dry-cured and E-E type 6.6kV XLPE cables removed after 18-25 years of operation and observed the water trees in their XLPE insulation. As a result, it was observed that breakdown voltages were larger than the maximum operating voltage (6.9kV) and the AC voltage for the dielectric withstanding test (10.3kV). Water trees were mainly bow-tie water trees and their maximum length was approximately 1mm. Although the number of measured cables was limited, the lifetime of this type of cable was estimated to be approximately 40 years, even experiencing water immersion.

収録刊行物

参考文献 (16)*注記

もっと見る

詳細情報 詳細情報について

問題の指摘

ページトップへ