Development of a Voltage Sag Detection Method for Non-Utility Generation System
-
- Uchiyama Noriyuki
- Power & Industrial Systems R&D Lab., Hitachi Ltd.
-
- Oono Yasunori
- Power & Industrial Systems R&D Lab., Hitachi Ltd.
-
- Fujita Yasunobu
- Power & Industrial Systems Division, Hitachi Ltd.
Bibliographic Information
- Other Title
-
- 自家用発電設備向け瞬時電圧低下検出手法の開発
- ジカヨウ ハツデン セツビ ムケ シュンジ デンアツ テイカ ケンシュツ シュホウ ノ カイハツ
Search this article
Abstract
This paper deals with a new detection method based on 3-phase vector operation for voltage sag. The detection method is applicable to a protection system using a high speed interruption system which protects distributed generators and critical loads in a customer’s facility. First, the algorithm and merits of this method are explained in detail. Secondly, the detection characteristics are analyzed using the ATP (Alternative Transients Program) and are confirmed using a real time digital simulator, and it is shown that the method is useful for detecting voltage sag.
Journal
-
- IEEJ Transactions on Power and Energy
-
IEEJ Transactions on Power and Energy 124 (4), 531-536, 2004
The Institute of Electrical Engineers of Japan
- Tweet
Keywords
Details 詳細情報について
-
- CRID
- 1390001204601573760
-
- NII Article ID
- 10012706012
-
- NII Book ID
- AN10136334
-
- ISSN
- 13488147
- 03854213
-
- NDL BIB ID
- 6908970
-
- Text Lang
- ja
-
- Data Source
-
- JaLC
- NDL
- Crossref
- CiNii Articles
-
- Abstract License Flag
- Disallowed