ホモトピー関数を用いた電圧・熱容量ATCの高速計算法の提案

書誌事項

タイトル別名
  • A Proposal of a Fast Computation Method for Thermal Capacity and Voltage ATC by Means of Homotopy Functions
  • ホモトピー カンスウ オ モチイタ デンアツ ネツ ヨウリョウ ATC ノ コウソク ケイサンホウ ノ テイアン

この論文をさがす

抄録

This paper proposes a fast computation method for Available Transfer Capability (ATC) with respect to thermal and voltage magnitude limits. In the paper, ATC is formulated as an optimization problem. In order to obtain the efficiency for the N-1 outage contingency calculations, linear sensitivity methods are applied for screening and ranking all contingency selections with respect to the thermal and voltage magnitude limits margin to identify the severest case. In addition, homotopy functions are used for the generator QV constrains to reduce the maximum error of the linear estimation. Then, the Primal-Dual Interior Point Method (PDIPM) is used to solve the optimization problem for the severest case only, in which the solutions of ATC can be obtained efficiently. The effectiveness of the proposed method is demonstrated through IEEE 30, 57, 118-bus systems.