For the suppression of metallic particle lift-off in compact Gas-Insulated-Switchgear (GIS), a coating with nonlinear resistivity characteristic was adapted to the inner surface of GIS tank. Electrical field analysis using the measured current density to electric field (J-E) characteristics indicates that the nonlinear resistivity coating can reduce the field enhancement between metallic particles and the coating effectively to suppress particle lift-off. Experiments using a coaxial GIS bus duct geometry indicate that the nonlinear resistivity coating increases the lift-off electric field of metallic particles with small statistical dispersion compared to a dielectric coating.