書誌事項
- タイトル別名
-
- Investigations Regarding a Mechanism and a Countermeasure Against the Phase-to-phase Short-circuit Fault due to Arc Jets Spouting from the Arcing Horns for 66kV Overhead Transmission Lines
- アークホーン カラ フキダスル アークジェット ニ ヨル 66kV カクウ ソウデンセン ノ ソウカン タンラク ハッセイ メカニズム オヨビ タンラク ボウシサク ニ カンスル ケントウ
この論文をさがす
抄録
On a 66kV overhead transmission line equipped with arcing horns, a two-phase short-circuit fault between an upper and a lower line caused by a lightning strike turned into a three-phase short-circuit fault. And, a round inspection after the fault revealed that there were many partially-melted spots on a jumper wire of middle line. In order to clarify the mechanism of the fault experimentally, the short-circuit tests were carried out by using the full scale apparatus considering the installation conditions of the arcing horns on the actual lines. The arc was ignited between arcing horns installed on the lower line, and the aspects of the phase-to-phase short-circuit fault between the lower and the middle line were observed by using the high speed videos. As a result, the arc jets spouted upwards from the arcing horns of the lower line, and the arc showed a tendency of rising easily due to the arc jets. These results suggested that the hot gas generated by the arc and the arc jets caused the breakdown between the lower and the middle line, and the phase-to-phase short-circuit fault occurred. Considering the breakdown phenomena, a countermeasure against the short-circuit fault was investigated.
収録刊行物
-
- 電気学会論文誌B(電力・エネルギー部門誌)
-
電気学会論文誌B(電力・エネルギー部門誌) 135 (6), 380-387, 2015
一般社団法人 電気学会
- Tweet
詳細情報 詳細情報について
-
- CRID
- 1390001204603544832
-
- NII論文ID
- 130005072604
-
- NII書誌ID
- AN10136334
-
- ISSN
- 13488147
- 03854213
-
- NDL書誌ID
- 026555512
-
- 本文言語コード
- ja
-
- データソース種別
-
- JaLC
- NDL
- Crossref
- CiNii Articles
-
- 抄録ライセンスフラグ
- 使用不可