An Efficient Faults Calculation Method Including Mutually Coupled Lines of Power System
-
- Tanaka Kazuyuki
- CRIEPI
Bibliographic Information
- Other Title
-
- 故障計算における零相回線間影響の効率的計算手法
- コショウ ケイサン ニ オケル レイソウ カイセンカン エイキョウ ノ コウリ
Search this article
Description
It is necessary to take the effects of mutual couplings into account when unbalanced faults are to be calculated in such as transient stability study.<br> When the method based on symmetrical co-ordinates is applied to faults calculation, it has been needed in conventional method to construct the zero sequence network configurated more complex than other networks so far. Then, the application of faults calculation including mutual couplings to the analysis on bulk power system model has been considerably difficult for long time.<br> This report presents the newly developed method to calculate the effects of mutual coupling in multi-faults calculation under same configuration and with no change for all sequence networks. The validity of proposed method was verified through the application to transient stability analysis for power system model.
Journal
-
- IEEJ Transactions on Power and Energy
-
IEEJ Transactions on Power and Energy 115 (2), 105-110, 1995