- A Verification of Automatic Frequency Controller for Minami-Fukumitsu Back-To-Back Converter Station
- ミナミ フクミツ チョクリュウレンケイ セツビ ニ オケル シュウハスウ アンテイカ セイギョ ノ ケンショウ
この論文をさがす
説明
Minami-Fukumitsu BTB (Back-To-Back) Converter Station is the first nonsynchronous link facility within the Japanese 60Hz system and it connects the system of Chubu Electric Power and Hokuriku Electric Power. An Automatic Frequency Controller (AFC) is installed in this facility to stabilize the frequency of the power system after a large disturbance (like one part of power system is divided from the other part) and to enhance suppression of frequency fluctuation.<br> This paper describes individual problems and countermeasures to install optimal multi-variable control AFC and introduces a part of test results using actual power system to verify performance of control systems. This paper also shows effectiveness of analysis using digital simulation tools.