Discussions on Lightning Discharge Parameters on Transmission Line by Altitude Triggered Lightning in Winter Thunderstorm
-
- Minowa Masayuki
- TOENEC Corporation
-
- Nakamura Koichi
- Nagoya Institute of Technology
-
- Wakamatsu Masatoshi
- Numazu College of Technology
Bibliographic Information
- Other Title
-
- ロケット手法を用いた冬季鉄塔誘雷による送電線雷撃パラメータの検討
- ロケット シュホウ オ モチイタ トウキ テットウ ユウライ ニヨル ソウデン
Search this article
Abstract
This paper presents the altitude triggered lightning to a test EHV transmission line in winter thund erstorm. The inducing wire was isolated with a nylon line from the ground up to the altitude of 70m to 160m. Thirty one striking events have taken place on the several locations of the transmission line. Current wave forms were measured and the corresponding lightning discharge channels were well reconstructed by an acoustic analyzing method. The characteristics of striking distance vs. peak current, and the histogram of vertical striking angle were investigated and discussed from the view point of lightning striking parameter to a transmission line.
Journal
-
- IEEJ Transactions on Power and Energy
-
IEEJ Transactions on Power and Energy 117 (4), 472-477, 1997
The Institute of Electrical Engineers of Japan
- Tweet
Keywords
Details 詳細情報について
-