The Concordia-Demello model is well known method for adjusting PSS constants of tandem type of generators and widely used. However, this method is not able to analyze a cross compound generator correctly which consists of primary and secondary generators and has a local and an interarea modes. Therefore, in order to adjust PSS constants of cross compound generator, a more detail model is required. Such researches are few and an efficient methodology that grasps characteristic of cross compound PSS with sufficient accuracy is strongly desired.<br> In this paper, the authors propose a method using the Park's model considering the damper effects, which can be obtained by linearizing a 2 generator to infinite bus system. The proposed method uses a torque coefficient matrix obtained from the linear state equation and calculates an electric torque by using it.<br> Firstly, this paper reveals the difference of electric torque characteristics between a tandem and a cross compound generator. Next, it points out that conventional methods that adjust PSS constant by evaluating a primary and a secondary generator separately may give wrong results. Finally, the effectiveness of the proposed method is confirmed by using a test model.