書誌事項
- タイトル別名
-
- Development of Partial Discharge Automatic Monitoring System for Extra-High Voltage XLPE Cable Lines Using Neural Network
- ニューラルネット ニ ヨル チョウコウアツ CV ケーブル センロヨウ ブブン ホウデン ジドウ カンシ システム ノ カイハツ
この論文をさがす
抄録
We have successfully put a new system into practice. The system is using a highly sensitive partial discharge (PD) method for live line power cables and automatic recognition of PD from external noise for long-distance cable lines, in order to ensure that extra-high voltage XLPE cable lines are proved to be reliable. In this system, signals from each joint in the underground tunnel are detected using a high frequency tuning method before they are optically transmitted to the master station for centralized monitoring of whole signals. The system has a primary recognition section which is composed of various analog gates and secondary section which is uses a neural network (NN) to automatically discriminate PD. The system is capable of highly sensitive(1-10pC) PD detection along the entire line. Application of the system to PD measurement in after laying test of 275kV XLPE cable lines demonstrated its automatic monitoring capabilities.
収録刊行物
-
- 電気学会論文誌B(電力・エネルギー部門誌)
-
電気学会論文誌B(電力・エネルギー部門誌) 119 (2), 195-203, 1999