最近の石油タンク爆発事故から考察する放爆構造

書誌事項

タイトル別名
  • A Consideration on Frangible Roof Joint Design due to Recent Oil Tank Explosion
  • サイキン ノ セキユ タンク バクハツ ジコ カラ コウサツ スル ホウバクコウゾウ

この論文をさがす

抄録

Two tank explosions simultaneously occurred at a salt water disposal facility in Lamesa, Texas on May 15, 2009. One tank launched as a skyrocket, and the roof plate separated and flew in the other tank at the explosion. The frangible roof joint is designed so that the strength of the sidewall-to-roof joint is weaker than that of the sidewall-to-bottom joint under overpressurization in aboveground oil storage tanks. This rule did not perform as intended in the tank which launched. This paper presents a consideration on the frangible roof joint design due to the tank explosion.