ON A NEW WAY TO OBTAIN ACCURATE WIND LOAD ON CLADDING

  • OKADA Hisashi
    Building Research Institute, Ministry of Construction
  • KONG Lingzhe
    The Boundary Layer Wind Tunnel Laboratory, The University of Western Ontario, Canada

Bibliographic Information

Other Title
  • 外装材風荷重の評価方法について
  • On a New Way to Obtain Accurate Wind Lo

Search this article

Abstract

Wind load on cladding is a very important parameter in building design, especially for high-rise buildings . So far in various building regulations and standards, the design wind load is defined as the difference of the maximum external pressure and the maximum internal pressure.<BR>However, depending on the sign of the internal pressure, this would result either overestimation or under-estimation of wind loads in most situations. In the present study, a proposal to calculate the design wind load accurately is investigated. A new concept of gust factor for the building internal pressure is introduced and its values in various conditions are recommended through wind tunnel test.