冷却塔白煙の可視領域予測に関する研究

書誌事項

タイトル別名
  • Study on Prediction of Visible Plume from Wet-type Cooling Tower

この論文をさがす

説明

In recent years in Japan, many electric power producers tend to construct small scalethermal power stations with wet-type cooling tower because of its cheapness compared with conventional sea-water-cooled system. However exhaust gas from wet-type cooling lower has much moisture and relatively high temperature, water vapor inside the plume becomes condensed when mixed with cool ambient air and this makes exhaust plume visible. This visible plume problem is one of the new environmental problem, because large visible plume which come down to the ground level can bring droplets which could be harmful and can also cause loss of light, low visibility and icing of roads, etc.<BR>In this study, for the purpose of prediction of behavior of visible plume, numerical simulation model which is able to take account of the effect of heat transfer due to phase change of water and gravity effects on the large droplets was developed. Its calculation results were compared with field observation data set of existing cooling towers.

収録刊行物

  • 日本風工学会誌

    日本風工学会誌 1998 (75), 43-48, 1998

    一般社団法人 日本風工学会

詳細情報 詳細情報について

  • CRID
    1390001204641621120
  • NII論文ID
    130004013647
  • DOI
    10.5359/jawe.1998.75_43
  • ISSN
    18838413
    09121935
  • データソース種別
    • JaLC
    • Crossref
    • CiNii Articles
  • 抄録ライセンスフラグ
    使用不可

問題の指摘