Detection of Zero-Sequence Current and its Current Sensor.
-
- Sonoda Toshikatsu
- Kyushu Institute of Technology
-
- Ueda Ryuzo
- Kyushu Institute of Technology
-
- Ohtsu Toshihiko
- Kyushu Electric Power Company
Bibliographic Information
- Other Title
-
- 零相電流検出と電流センサ
- レイソウ デンリュウ ケンシュツ ト デンリュウ センサ
Search this article
Abstract
The purpose of this paper is to give a basis for developing a current sensor which can contribute to the improvement of reliability in power supplies by detecting faint faults early in the deterioration of insulation in distribution lines, Thus, we develop a method of detecting the zero-sequence current: (i) Each current sensor of the same detection accuracy is installed to each line of the three phase and (ii) Zero-sequence current is identified as a summation of the output signal in each sensor. The detection performance which can be achieved is: For the main current of 100 A, we can detect the zero-sequence current of 0.1 A with the accuracy of 3% regarding the 100% error.
Journal
-
- IEEJ Transactions on Industry Applications
-
IEEJ Transactions on Industry Applications 113 (2), 179-188, 1993
The Institute of Electrical Engineers of Japan