- Numerical Analysis on Optimization of a Fin and Tube Type Adsorber/Desorber Heat Exchanger using ACF/C<Sub>2</Sub>H<Sub>5</Sub>OH Pair
- ACF/C2H5OH系フィンチューブ式吸着器の最適設計に関する解析
- ACF C2H5OHケイ フィンチューブシキ キュウチャクキ ノ サイテキ セッケイ ニ カンスル カイセキ
この論文をさがす
抄録
This study deals with a two dimensional numerical analysis of the fin and tube type adsorber/desorber heat exchanger design such as fin height, fin pitch, fin thickness and tube diameter effect on the performance of closed adsorption cooling system with activated carbon fiber (ACF) of type A-20, which has relatively higher surface area, and ethanol pair. The simulation results show that the fin tube diameter is effective on the performance of the heat exchanger. It is also found that the cycle COP can be optimized in the condition of fin pitch 4.5mm and fin height 20mm, respectively when other parameters are fixed.