- Experimental Investigations on the Characteristics of the Ammonia-Water Absorption Refrigerator for Low Temperature Solution Cycle
- テイオン レイトウヨウ アンモニア スイケイ キュウシュウ レイトウキ ノ
この論文をさがす
抄録
This report refers to some static characteristics of the ammonia-water absorption refrigerator for low temperature refrigerating process which needs the temperature below the freezing point. Especially, the influence of evaporating temperature and cooling water temperature is clarified by the experimental investigation. In addition to this, the validity of constructed simulation model of this absorption refrigerator is mentioned. The validity of simulation model is verified by the comparison of experimental results and calculation. <br>To examine the characteristics, we conducted the performance test using the trial product of which the standard cooling capacity is 175kW. The performance is estimated according to cooling capacity and COP. As a result, the effects of the evaporating temperature and cooling water temperature on the cooling performance are clarified by the experimental research. Furthermore, the calculation of the static characteristics predicted by the simulation model is in good agreements with the experimental results.