THE EFFECTIVE RADIATOIN AREA AND CONFIGURATION FACTOR FOR THE PERSON SITTING ON A FLOOR
-
- MIYAMOTO Seiichi
- Dept. of Architecture, Faculty of Engineering, Nagoya Institute of Technology
-
- TANIGUCHI Yoshiki
- Shin-Nihon-Kuchyou Corporation
-
- Choi Young Sik
- Dept. of Architecutre, Yeungnam Junior College
-
- TSUCHIKAWA Tadahiro
- Dept. of Architecture, Gifu National College of Technology
-
- HORIKOSHI Tetsumi
- Dept. of Architecture, Faculty of Engineering, Nagoya Institute of Technology
Bibliographic Information
- Other Title
-
- 床座時の人体有効放射面積と形態係数に関する研究
- ショウザジ ノ ジンタイ ユウコウ ホウシャ メンセキ ト ケイタイ ケイスウ
Search this article
Description
The effective radiation area factors and configuration factors for male and female subjects sitting on the floor were measured by the photographic method. Contacted surface area with a floor was excluded for calculation of radiation area. The effective radiation area factor was found to be 0.64 for an unclothed male, 0.71 for a clothed male, 0.62 for an unclothed female, and 0.66 for a clothed female. Diagrams of configuration factors between the human body sitting on the floor and rectangular planes were represented for the combination of clothing and posture.
Journal
-
- Journal of Architecture and Planning (Transactions of AIJ)
-
Journal of Architecture and Planning (Transactions of AIJ) 61 (479), 27-33, 1996
Architectural Institute of Japan
- Tweet
Details 詳細情報について
-
- CRID
- 1390001204781507968
-
- NII Article ID
- 110004654202
- 10007243538
-
- NII Book ID
- AN10438548
-
- ISSN
- 18818161
- 13404210
-
- NDL BIB ID
- 3916318
-
- Text Lang
- ja
-
- Data Source
-
- JaLC
- IRDB
- NDL
- Crossref
- CiNii Articles
-
- Abstract License Flag
- Disallowed