MEAN RADIANT TEMPERATURE CONSIDERING THE EFFECT OF INTER-REFLECTIONS AND BLOCKING EFFECT OF THE HUMAN BODY USING NET REDIATION METHOD

Bibliographic Information

Other Title
  • 相互反射及び人体による遮蔽の影響を考慮した平均放射温度に関する研究
  • ソウゴ ハンシャ オヨビ ジンタイ ニヨル シャヘイ ノ エイキョウ オ コウ

Search this article

Abstract

The objective of this paper is to evaluate the thermal radiation environment using mean radiant temperature MRTr which takes configuration factors and equivalent black body temperatures the effect of the inter-reflection and blocking effect of the human body. Numerical analysis of inter-reflection radiant exchange were carried out using Net Radiation method. MRTr was calculated from radiation rate, emissivity and configuration factors on each surface. As a result, The difference between the MRT considering the effect of inter-reflection and the ordinary MRT stood within ±3℃ when the emissivity of a floor changed from 0.50 to 1.00 under the following floor heating condition : the floor surface temperature 37.5℃ and the other surface temperature 21℃. The MRT was influenced by emissivities of each surface in the non-uniform thermal radiation environments rather than uniform environment. It is necessary to evaluate the non-uniform thermal radiant environment using the MRT considering the effect of radiation inter-reflection and blocking effect of the human body.

Journal

Citations (2)*help

See more

References(12)*help

See more

Details 詳細情報について

Report a problem

Back to top