高層建築物避難を想定した階段室における在館者群集の合流特性

書誌事項

タイトル別名
  • CHARACTERISTICS OF CONFLUENCE OF TWO OCCUPANT FLOWS AT STAIRCASE OF HIGH-RISE BUILDING
  • コウソウ ケンチクブツ ヒナン オ ソウテイ シタ カイダンシツ ニ オケル ザイカンシャ グンシュウ ノ ゴウリュウ トクセイ

この論文をさがす

抄録

In a case of fire at high-rise building or complex usage building, many evacuees uses staircase at once. At the staircase, confluence is happened between the evacuees from upper floors and ones entering to the staircase. The condition of merging may have impact on escape time, not only on the fire floor but also the time in the whole building. However there is less research about the condition of merging about staircase. The purpose of this study was to investigate the effects of merges in stair case and easiness of merging in various cases. The tests were conducted to compare different cases in: 1) crowd density, 2) directions of merges, 3) door open or close. The results lead to the following conclusions: 1) it is easier to merge at lower density; 2) it is easier to merge if the direction of the merging crowd is same as the direction of the crowd in staircase; 3) it is easier to merge if the door is open, and it lowers the evacuation flow rate by 70% at the door when the door is closed at start.

収録刊行物

被引用文献 (4)*注記

もっと見る

参考文献 (8)*注記

もっと見る

詳細情報 詳細情報について

問題の指摘

ページトップへ