抄録

Pressure drop between drum and receiver is nearly proportional to the square of steam flow. Pressure at receiver has two effects of drum pressure and steam flow. In this system the fuel and air are controlled proportionately the pressure difference between pre-set normal drum pressure and receive pressure. The pressure difference is measured by a piston type pressure gauge. The transient response of drum pressure by step load change (a·normal load) is [number formula] where [number formula] α : pressure drop between drum and receiver divided by normal drum pressure ρ : Time constant of thermal capacity divided by time constant of heat transmission τ : real time divided by time constant of thermal capacity