- LONG-TERM EVALUATION ON EMISSION OF FORMALDEHYDE USING EXPERIMANTAL MODEL ROOMS WITH DIFFERENT VENTILATION RATES
- ジッケン ジュウタク オ モチイタ コトナル カンキリョウ カ ニ オケル ホルムアルデヒド チョウキカン ホウサン ニ カンスル ケンキュウ
この論文をさがす
抄録
The concentrations of formaldehyde and the ventilation rates were measured in an experimental house for two years. The emission rates from the materials were separately measured by using of a small chamber. It was found that the concentrations in the house was increased during the summer season. The total emission amount in the ventilated room was about 10 times as large as that in the non-ventilated room. The emission rates from the materials in the ventilated room were 70% of those from the materials in the non-ventilated room. Emission from particle board was lasted for two years experiment.