- VERIFICATION OF THE EFFECT OF SUNSHADING TECHNIQUES INTRODUCED TO WALLS AND ROOFS THROUGH THE MEASUREMENT AT THE TWO TEST HOUSES
- Study on calculation method for the evaluation of sunshading and insulating effect of the walls and roofs with vented air-layer (Part 4)
- 通気層を有する外壁・屋根の遮熱・断熱効果の計算法に関する研究(その4)
- 公開日
- 2010
- DOI
-
- 10.3130/aije.75.139
- 公開者
- 日本建築学会
この論文をさがす
説明
Indoor thermal comfort and energy consumption during summer season are greatly influenced by the radiant heat from windows as well as walls and ceilings. The objective of this report is to compare the surface temperatures of the second floor room of the two test houses, one with sunshading techniques and the other without them, and to verify the proposed calculation method by comparing calculated indoor surface temperatures with measurements. The following results were obtained.<br> (1) The surface temperatures of the test house with sunshading techniques were lower than those of the test house without sunshading techniques during summer, while as the same level as them during winter.<br> (2) The calculated surface temperatures well agreed with the measurements.