A-20 給水・給湯さや管ヘッダー工法の更新性に関する研究 : 第1報 架橋ポリエチレン管の劣化調査
書誌事項
- タイトル別名
-
- A-20 Research on Renewability of Cold and Hot Feedwater Header-Conduit Piping System : Part 1 ; Study of deterioration of cross-linked polyethylene (PEX)
- 公開日
- 2007
- DOI
-
- 10.18948/shasetaikai.2007.2.0_687
- 公開者
- 公益社団法人 空気調和・衛生工学会
この論文をさがす
説明
PEX pipe is widely used as the material of pipes for water supply including hot water. We used sample pipes that had been used in the field for approximately 15 years to examine their deterioration conditions through mechanistic diagnosis (i.e. tensile strength test, bend test, etc.) and chemical diagnosis (i.e. heat aging test). The results suggest no evidence of deterioration of the pipes for both cold and hot water. OIT shows that the coupling of hot water feed pipes had the maximum deterioration. However, it was assumed that its remaining life should be approximate 60 years.
収録刊行物
-
- 空気調和・衛生工学会大会 学術講演論文集
-
空気調和・衛生工学会大会 学術講演論文集 2007.2 (0), 687-690, 2007