INJECTION AND EXTRACTION OF GROUND HEAT BY BORE-HOLE HEAT EXCHANGE SYSTEM AND KONG PERIOD THERMAL INTERACTION BETWEEN GROUND AND BORE-HOLE

Bibliographic Information

Other Title
  • 熱交換掘削杭の採・放熱特性および地盤との長期熱的相互作用
  • ネツコウカン クッサク クイ ノ サイ ホウネツ トクセイ オヨビ ジバン ト ノ チョウキ ネツテキ ソウゴ サヨウ

Search this article

Abstract

Thermal energy performance of a Bore-hole Heat Exchange System (BHES) was studied through field experiments and computations. From the comparison of experimental data on fluid temperature profiles in the bore-hole with numerical results, it was seen that a proposed numerical model is reliable and effective for numerical experiments to comprehend the annual and seasonal energy changes associated with the injection and extraction of the BHES. The present computation could offer significant information with respect to the effects of the bore-hole length, fluid flow rate and circulation direction of the fluid in the bore-hole on the heat transfer capacity between the bore-hole and the surrounding ground. It also indicated that the injection to the ground of the surplus heat in summer leads to the increase in the extraction of the ground heat in winter of 3% ten years later.

Journal

Citations (2)*help

See more

References(18)*help

See more

Details 詳細情報について

Report a problem

Back to top