耐火塗料の耐火性能に及ぼす鉄骨部材の熱容量の効果

書誌事項

タイトル別名
  • EFFECT OF HEAT CAPACITY OF STEEL MEMBERS ON THE FIRE RESISTANCE OF INTUMESCENT COATING
  • タイカ トリョウ ノ タイカ セイノウ ニ オヨボス テッコツ ブザイ ノ ネ

この論文をさがす

説明

As intumescent coating has lower level of insulation than ordinary protective materials, we have already reported that a period of fire resistance not less than one hour was obtained by using Fire Resistant steel which has a higher strength at high temperatures. As the actual steel sections used for multi-stroy buildings are usually heavier than that of the sections used in standard fire tests, the steel temperature is relatively low because of their heat capacities. This paper presents experimental results of the heat test of steel members coated by an intumescent coating with various heat capacities. By simulating the measured steel temperatures, design diagrams for determining the coating thickness were obtained.

収録刊行物

被引用文献 (2)*注記

もっと見る

キーワード

詳細情報 詳細情報について

問題の指摘

ページトップへ