114 清掃工場の押込送風機風路で発生した低周波振動((1)低周波・超低周波音の最新技術,騒音・振動改善技術)

書誌事項

タイトル別名
  • 114 Low Frequency Vibration at Air Supply Duct Induced by Forced Draft Fan in Refuse Incineration Plant

この論文をさがす

説明

Some trouble of low frequency vibration had been occurred at the new refuse incineration plant. Low frequency noise and vibration were induced around the forced draft fan when the draft fan was operated in the condition of low flow rate by controlling the floe valve. It was practically estimated with depending on the result of some measurements and analysis on the site that the acoustic resonance in the air supply duct and the vibrant resonance on the delivery silencer were excited by the low frequency pulsation of the discharge flow from the centrifugal fan. This trouble has been resolved by the reinforcement of the silencer and by the additional set up of the returning by-pass duct from the outlet to the suction side of the fan. It would be the next stage problem for solutions that mechanisms of low frequency pressure fluctuations induced by the special fan with high pressure and wide range of flow rate are made clear.