Flow in a Pipe Fitting : Part 2-Energy Loss of Turbulent Flow in a Pipe Fitting with Branching Angle of 90-deg. and also with Rounding or Chamfering
-
- SUU Tetsuo
- Faculty of Education, Shinshu University
-
- FUJII Kiyomi
- Oyama Vocational Training College
-
- TANAMI Seiichi
- Nissan Motor Co., Ltd.
-
- SATO Mototaro
- Faculty of Engineering, Shinshu University
Bibliographic Information
- Other Title
-
- 割込み型分岐管内の流れ : 第2報-分岐角度が90°で枝管入口に丸みまたは面取りを有する場合の乱流におけるエネルギ損失
- 割込み型分岐管内の流れ-2-分岐角度が90°で枝管入口に丸みまたは面取りを有する場合の乱流におけるエネルギ損失
- ワリコミガタ ブンキカンナイ ノ ナガレ 2 ブンキ カクド ガ 90 デ シ
Search this article
Abstract
As one of the attempts to reduce the energy loss of turbulent flow in the pipe fittings with a branching angle of 90-deg., the pipe fittings with different rounding and chamfering sizes at the up- and downstream edges of the lateral entrance are prepared. The pipe fittings under experiment have three areal ratios and rectangular crosssection. The aspect ratio of the conduit, which denotes a ratio of the depth to the width of the conduit, is common for practical use. The amount of the rounding and chamfering sizes is twenty-seven. The energy loss coefficients for the flow from the main conduit into the lateral conduit and for the straight-through flow and also the power-loss coefficient were measured and discussed. As the results, the energy loss coefficients for the pipe fitting with rounding are, generally, smaller than those with chamfering. Moreover, it is clarified that the energy loss becomes small when the sizes of rounding and chamfering are the same as those of the width of the lateral conduit. The empirical formulae for the energy loss coefficients for the flow from the main conduit into the lateral conduit and for the straight-through flow are decided at the above sizes of rounding and chamfering.
Journal
-
- Transactions of the Society of Heating,Air-conditioning and Sanitary Engineers of Japan
-
Transactions of the Society of Heating,Air-conditioning and Sanitary Engineers of Japan 13 (36), 11-19, 1988
The Society of Heating, Air-Conditioning & Sanitary Engineers of Japan