Evaluation on Oxygen Permeation of Plastic Pipes for Hot Water Heating System

Bibliographic Information

Other Title
  • 温水暖房用プラスチック管の酸素透過に関する評価
  • オンスイ ダンボウヨウ プラスチックカン ノ サンソ トウカ ニ カンスル ヒョウカ

Search this article

Description

In this thesis, the oxygen permeation of the plastic pipe in hot water heating system was evaluated in order to discuss the influence of the corrosion of steel radiators in the same line. The oxygen permeability rate of the polyethylene bridge pipes, the polybutene pipes, and the polypropylene pipes was 5.9〜15.5mgO/(L・日), and that of the polyethylene bridge pipes with the oxygen interception layer was less than 0.1mgO/(L・日) in the average temperature 40℃. The plastic pipes with the oxygen interception layer were prevented to penetrate the oxygen from air, and were able to be allowed to use for the main pipes and the floor heating pipes in terms of the corrosion protection of the radiators, and it was showed that the plastic pipes with the oxygen interception layer were effective for the corrosion protection of steel radiators.

Journal

Citations (2)*help

See more

References(8)*help

See more

Details 詳細情報について

Report a problem

Back to top