Comparison of Dynamic Calculation for Air Conditioning Load and Actual Energy Consumption for Air Conditioning
-
- NANRI Hiroyoshi
- Department of Architectual Equipment Engineering, Kurume Institute of Technology
-
- WADA Masato
- Department of Architecture, Faculty of Engineering, Kyushu University
-
- URANO Yoshimi
- Department of Architecture, Faculty of Engineering, Kyushu University
Bibliographic Information
- Other Title
-
- 動的熱負荷計算結果と実際の空調熱源用エネルギ消費量の比較
- ドウテキ ネツ フカ ケイサン ケッカ ト ジッサイ ノ クウチョウ ネツゲン
Search this article
Description
This paper searches for the reason for the difference between the air-conditioning load calculation by HASP/ACLD/8001 and air-conditioning energy consumption. The causes of the difference between AHET and cooling energy consumption are cooling period, whether there is package unit or fancoil unit, density of the inside illumination and draft load. The difference can be explained by these factors. And AHET is greater than the actual energy consumption. The difference between AHST and heating energy consumption is caused by the heating period, whether or not air-conditioning uses an air source or water source area of windows, total floor space and the existence of peaple. But it cannot be explained by these factors as in the case of cooling.
Journal
-
- Transactions of the Society of Heating,Air-conditioning and Sanitary Engineers of Japan
-
Transactions of the Society of Heating,Air-conditioning and Sanitary Engineers of Japan 9 (25), 41-50, 1984
The Society of Heating, Air-Conditioning & Sanitary Engineers of Japan
- Tweet
Details 詳細情報について
-
- CRID
- 1390001206546149120
-
- NII Article ID
- 110007864327
-
- NII Book ID
- AN00065706
-
- ISSN
- 24240486
- 0385275X
-
- NDL BIB ID
- 3017276
-
- Text Lang
- ja
-
- Data Source
-
- JaLC
- NDL Search
- CiNii Articles
-
- Abstract License Flag
- Disallowed