Development of an Adsorption Refrigerator with Regenerative Adsorbent Working at Low Temperature

DOI

Bibliographic Information

Other Title
  • 低温再生型吸着材を用いた吸着式冷凍機の開発
  • Part 3-Controlling the Cold-Water Temperature at the Outlet by Adjusting the Cooling Water Flow Rate
  • 第3報−冷却水バイパス流路による冷水出口温度一定化の検討

Abstract

<p>An adsorption refrigerator with a zeolite adsorbent can be regenerated using water at a low temperature of 45 to 60 ℃. In this refrigerator, the cold water outlet temperature fluctuates, and with increase in the cycle time, the fluctuation range becomes larger. Therefore, it may be difficult to use this in air conditioning applications or applications requiring accurate water supply temperature. In a previous study, the amount of cooling water supplied to a heat exchanger (HEX) coated with an adsorbent was varied to maintain a constant cold-water temperature at the outlet. However, it was found that the cooling capacity reduces after the subsequent cycle. In the previous system, when the amount of cooling water supplied to the HEX decreases, the amount of cooling water supplied to the condenser also decreases, because the HEX and condenser are connected in series through a cooling pipe. In this study, we installed a bypass route from the inlet side of the HEX to the condenser in order to maintain the amount of cooling water supplied to the condenser in a stable manner. Then, we measured the temperature change of the cold water and the cooling capacity. We confirmed that the mean deviation of the cold-water outlet temperature could be improved to within ±0.2℃ by reducing the output to 80-90% of the steady-state cooling capacity. </p>

Journal

Details 詳細情報について

  • CRID
    1390002184861352960
  • NII Article ID
    130007782497
  • DOI
    10.18948/shase.44.262_15
  • ISSN
    24240486
    0385275X
  • Text Lang
    ja
  • Data Source
    • JaLC
    • CiNii Articles
  • Abstract License Flag
    Disallowed

Report a problem

Back to top