A Study on Recovery Voltage during Capacitive Current Interruption on High Resistance Earthed Neutral Systems (3)
-
- Yanagi Kosuke
- Toshiba Energy Systems & Solutions Corporation
-
- Toyoda Mitsuru
- Toshiba Energy Systems & Solutions Corporation
-
- Nakakoji Hajime
- TEPCO Power Grid, Inc.
-
- Ito Yasunori
- Chubu Electric Power Co., Inc.
-
- Koga Takaki
- Kansai Electric Power Co., Inc.
Bibliographic Information
- Other Title
-
- 高抵抗接地系における進み小電流遮断時の回復電圧に対する考察(3)
- コウテイコウ セッチケイ ニ オケル ススミ ショウデンリュウ シャダンジ ノ カイフク デンアツ ニ タイスル コウサツ(3)
Search this article
Abstract
<p>The recovery voltages between contacts of circuit-breaker during capacitive current interruption on transmission lines with high resistance earthed neutral system were investigated. Actually operating transmission line systems including multi-parallel circuits, with cables and with branch circuits are modeled and recovery voltages during capacitive current interruption are investigated. All the results indicate that the recovery voltages for cases with high resistance earthed neutral system and with direct earthed neutral system are almost the same.</p>