Charging Potential Measurement of Floating Electrode Modeled on the Arc Shield of Vacuum Interrupter under AC Voltage Application

Bibliographic Information

Other Title
  • 真空インタラプタ内部のアークシールドを模擬した浮遊電極の帯電測定
  • シンクウ インタラプタ ナイブ ノ アークシールド オ モギ シタ フユウ デンキョク ノ タイデン ソクテイ

Search this article

Abstract

<p>A charging potential of a floating electrode modeled on vacuum interrupter was measured under unipolar AC voltage application using a surface potential meter. As a result, when a lower voltage was applied to the samples, only an induced potential depending on the electrostatic capacities of the sample and surrounding objects around the sample was measured from the floating electrode. However, in the case of high voltage application, not only induced voltage but also a positive charging potential was observed from the floating electrode which was enough to change the potential of the floating electrode. This is due to the field electron emission from the floating electrode itself.</p>