A Low Voltage Ride Through Control Method Based on a Virtual Impedance for a Grid Forming Inverter
-
- Kudo Yuki
- Toshiba Energy Systems & Solutions Corporation
-
- Kawachi Shunsuke
- Toshiba Energy Systems & Solutions Corporation
-
- Toba Koji
- Toshiba Energy Systems & Solutions Corporation
Bibliographic Information
- Other Title
-
- 系統電圧低下に対するGrid Formingインバータの仮想インピーダンス方式Fault Ride Through制御の検討
Description
<p>Grid forming inverters are expected to be installed in the utility grid in the near future, because they can provide inertia and short circuit capacity that are likely to decrease due to abolishment of thermal power plants. Also, these inverters have the advantage of enabling stand-alone operation for microgrid or business continuity plan. Since a conventional grid following inverter controls its output current directly, it is easy to prevent overcurrent in an event of a grid fault. On the other hand, a grid forming inverter works as a voltage source, therefore it is a challenge to limit its output current. This paper provides a low voltage ride through control method for a grid forming inverter, which is based on a virtual impedance. It realizes reliable current limitation and stable operation. The effectiveness of the proposed control method is verified by EMT simulation.</p>
Journal
-
- IEEJ Transactions on Power and Energy
-
IEEJ Transactions on Power and Energy 144 (4), 270-279, 2024-04-01
The Institute of Electrical Engineers of Japan
- Tweet
Details 詳細情報について
-
- CRID
- 1390018198841601280
-
- ISSN
- 13488147
- 03854213
-
- Text Lang
- ja
-
- Data Source
-
- JaLC
- Crossref
-
- Abstract License Flag
- Disallowed