三浦ダムの取水塔に対する寒中コンクリートを用いた補修工事

書誌事項

タイトル別名
  • Concrete Placing during Freezing Weather for Repair of Miura Dam's Intake Tower
公開日
1997
DOI
  • 10.11315/jsde1991.7.40
公開者
一般社団法人 ダム工学会

この論文をさがす

説明

Concrete placing was carried out during freezing weather in winter at the Miura dam to repair its intake tower, which had produced visible degradation in concrete after 70 years of service. The facility, located in mountainous terrain in central Japan and used exclusively for electric power generation, performs its flow-regulating duty throughout the year and, thus, there were restrictions on the method and timing of repair work to minimize adverse impact on power generation. The work was executed in winter when freezing weather prevails but the level of water in the reservoir remains relatively low. Lithium nitrite was used as an admixture in concrete in a bid to compensate for lack of sufficient curing time and to prevent initial frost damage. It was confirmed that the quality of concrete can be assured by adding lithium nitrite without the need for providing any special curing process, such as thermal insulation or heating.