シクロヘキサノンを含む溶剤の回収における活性炭の着火現象とその防止方法

書誌事項

タイトル別名
  • Ignition phenomenon of activated carbon bed during the recovery of cyclohexanone-containing solvent and its prevention.
  • シクロヘキサノン オ フクム ヨウザイ ノ カイシュウ ニ オケル カッセイタ

この論文をさがす

説明

In the recovery plant for solvent containing cyclohexanone (hereafter called as “anone”), there is a great possibility of heating and further ignition of the activated carbon bed due to the higher reactivity of anone and the catalytic effect of the activated carbon. Some basic experiments were carried out and the possibility of ignition of activated carbon beds and the methods of preventing it were studied. It was found that ignition of activated carbon was caused by the heat of oxidation of anone to CO or CO2. Further, reaction rate constants and activation eneries of the reaction were obtained for several carbons. Effective methods of preventing ignition of activated carbon were conduded to be as follows.<BR>(1) Use of activated carbon of low catalytic effect having larger micropore volume, developed for anone recovery.<BR>(2) Sufficient desorption of anone from the carbon bed and replacement of the air in the adsorption bed with an inert gas such as nitrogen during plant shutdown.<BR>(3) AvoidaRce of temperature distribution and of distribution of residual anone in the adsorption bed.

収録刊行物

被引用文献 (3)*注記

もっと見る

詳細情報 詳細情報について

問題の指摘