測定ケーブルが雷インパルス電圧波形パラメータに及ぼす影響

書誌事項

タイトル別名
  • Influences of a Measuring Cable Over the Lightning Impulse Parameters
  • ソクテイ ケーブル ガ カミナリ インパルス デンアツ ハケイ パラメータ ニ オヨボス エイキョウ

この論文をさがす

抄録

Influences of a co-axial measuring cable have been neglected in the lightning impulse measurements. This is partly because an allowable uncertainty for determining the front-time, T1, in the reference measuring system is 3% and the induced influence by using a long measuring cable is expected to be much smaller than the margin. The authors have so far suspected the validity of this argument through experience. This paper proposes analytical treatment of impulse response at the end of a lossy cable. Using the proposed expression, measured parameter errors are compared to the numerically evaluated ones and it is to be confirmed that both are in good agreement.

収録刊行物

参考文献 (3)*注記

もっと見る

関連プロジェクト

もっと見る

詳細情報 詳細情報について

問題の指摘

ページトップへ