- Evaluation of Magnetic Field Generated by Power Distribution Equipment in Accordance with IEC 62110
- IEC 62110 ニ ジュンキョ シタ ハイデンヨウ キキ カラ ハッセイ スル ジカイ ノ ヒョウカ
この論文をさがす
抄録
This paper reports results of magnetic field measurements around power distribution equipment i.e. pad-mounted transformers, pad-mounted switchgears and vertical cables. Measurements were carried out in accordance with IEC 62110 which prescribes measurement and evaluation procedures of non-uniform as well as uniform magnetic fields generated by ac power systems with regard to public exposure. The average exposure level of magnetic field, corresponding to the spatial average over entire human body of magnetic field to which the individual is exposed, was evaluated for each power distribution equipment based on the measurement results. The maximum exposure level, the highest average exposure level over the area of interest, was also obtained. It was found that both exposure levels are much lower than the reference level from the ICNIRP Guidelines published in 2010.
収録刊行物
-
- 電気学会論文誌. A
-
電気学会論文誌. A 135 (5), 282-286, 2015
一般社団法人 電気学会