共振電流を利用した低圧配電系統背後インピーダンスの推定

DOI DOI Web Site Web Site Web Site ほか1件をすべて表示 一部だけ表示 参考文献20件

書誌事項

タイトル別名
  • Estimation of Backward Impedance on Low-Voltage Distribution System using Measured Resonant Current
  • キョウシン デンリュウ オ リヨウシタ テイアツ ハイデン ケイトウ ハイゴ インピーダンス ノ スイテイ
  • Estimation of backward impedance on low‐voltage distribution system using measured resonant current

この論文をさがす

説明

Two estimation methods for a backward impedance of a power distribution system are proposed in this paper. A frequency response of a transient current flowing into a capacitor, which connected to a distribution line, has information of the backward impedance. The impedance is obtained from an attenuation constant and a resonance frequency determined by the capacitance and the impedance of power distribution system. These parameters are stably obtained from a frequency response of the transient current using a least square method. The accuracy of the method heavily depends on the origin on the time-axis for Fourier transform. Additional time-origin estimation is required for an accurate estimation of the backward impedance. The second method estimates the backward impedance using two transient current waveforms obtained by connecting alternately different capacitors to a distribution line. The backward impedance can be represented as a function of the frequency responses of these current. This method is suitable for an automatic measurement of the backward impedance because the method is independent from the time-origin. The proposed methods are applicable to an estimation of a harmonic current of the distribution system. In this paper, a harmonic current flowing through a distribution wire is estimated from the estimated backward impedance and the measured results of harmonic voltages obtained by an instrument developed by the authors.

収録刊行物

参考文献 (20)*注記

もっと見る

関連プロジェクト

もっと見る

詳細情報 詳細情報について

問題の指摘

ページトップへ