高圧設備用広帯域CTに対応したディジタルリレーの開発

書誌事項

タイトル別名
  • Development of a Digital Protection Relay Corresponding with a Multi-range Current Transformer for High Voltage Equipments
  • コウアツ セツビヨウコウタイイキ CT ニ タイオウ シタ ディジタル リレー ノ カイハツ

この論文をさがす

抄録

In the past, a current transformation ratio of a current transformer (CT) has been different for each facility corresponding with a rated current of a primary circuit in high voltage (6kV) equipments. By unifying specifications of a CT, there is no need to prepare a CT with various ratings corresponding with a capacity of a load facility, it becomes easier for consumers to modify facilities, and for manufacturers, it enables to standardize of a design and shorten a production period. Recently, it has been popular composition of a secondary circuit of a CT being connected with a digital protection relay bundled with protection and measurement functions not being connected with relays, meters and transducers separately. Because the composition enables to reduce a burden of a secondary circuit of a CT, reduction in size and weight of a CT is achieved and it also contributes to reduce a size of a cubicle and improve a mounting efficiency of a panel. We have developed a CT corresponding with a multi range input (a multi-range CT) and a digital protection relay utilizing its advantages which enable to standardize of a facility design and reduce a size of a cubicle, and report them in this paper.

収録刊行物

参考文献 (1)*注記

もっと見る

詳細情報 詳細情報について

問題の指摘

ページトップへ