変電所における計測電圧特異現象の解明

書誌事項

タイトル別名
  • Elucidation of a Peculiar Phenomenon of Voltage Measuring at a Substation
  • ヘンデンショ ニ オケル ケイソク デンアツ トクイ ゲンショウ ノ カイメイ

この論文をさがす

説明

An automatic fault-recorder installed in a substation of Chubu Electric Power Company detected a peculiar phenomenon that bus-bar voltage fell to around 20-30% of the nominal value for a short time (about 8-10 cycles) though electric current didn't change during the period. The phenominon was recorded several times.<br>In this paper, we analyzed the origin of this phenomenon and conducted simulations by EMTP. As a result, we estimated that this phenomenon occurred by the saturation of VT (voltage transformer), and this saturation caused by lightning strokes to the transmission line with line arresters, which have been increasingly installed in recent years. Moreover, we evaluated the influence of the phenomenon to protection relays.