Effect of Core Diameter of Cylindrical Polymer Insulators on Contamination Flashover Voltage(Part 2)
-
- Gautam Basanta Kumar
- Department of Electrical Engineering, Chubu University
-
- Matsumura Shigeki
- Department of Electrical Engineering, Chubu University
-
- Sakanishi Kenji
- Department of Electrical Engineering, Chubu University
-
- Kawaguchi Toshiyuki
- Department of Electrical Engineering, Chubu University
-
- Matsuoka Ryosuke
- Department of Electrical Engineering, Chubu University
-
- Ito Masatoshi
- The Japan Electrical Consulting Co. Ltd.
書誌事項
- タイトル別名
-
- Effect of Core Diameter of Cylindrical Polymer Insulators on Contamination Flashover Voltage-Part II
この論文をさがす
抄録
This paper presents the results of an investigation of the contamination flashover voltage characteristics of cylindrical polymer insulators with different core diameters under simulated rain. The specimens had the same or very similar shed profiles but different core diameters. On the contrary to the results obtained under heavy fog conditions, flashover voltages of transmission line insulator with the smallest core diameter were not significantly higher compared with those of station insulators having larger core diameters, such as station post insulators and bushing shells. The dominant flashover mechanism of hydrophobic polymer insulators under contaminated and rain conditions is water streaming along the insulator surface and the bridging between the adjacent shed tips by dripping water irrespective of core diameter. So, the flashover voltage of a contaminated cylindrical polymer insulator is not significantly influenced by its core diameter under rain conditions. Based on our investigation results, combined with the results obtained under heavy fog conditions reported in our companion paper (part I), it can be said that contamination flashover/withstand voltage tests may be conducted only under heavy fog conditions for evaluating polymer insulators having larger core diameters, while tests under simulated rain conditions as well as under heavy fog conditions may be necessary for evaluating transmission line polymer insulators having the smallest core diameter. The investigation results of flashover voltage characteristics of hydrophobic polymer insulators presented in this paper will be helpful in the selection, design and maintenance of polymer insulators for contamination areas.
収録刊行物
-
- 電気学会論文誌B(電力・エネルギー部門誌)
-
電気学会論文誌B(電力・エネルギー部門誌) 127 (1), 307-313, 2007
一般社団法人 電気学会
- Tweet
キーワード
詳細情報 詳細情報について
-
- CRID
- 1390282679579193088
-
- NII論文ID
- 10018456764
- 30027012309
-
- NII書誌ID
- AN10136334
-
- ISSN
- 13488147
- 03854213
-
- NDL書誌ID
- 8626269
-
- 本文言語コード
- en
-
- データソース種別
-
- JaLC
- NDL
- Crossref
- CiNii Articles
-
- 抄録ライセンスフラグ
- 使用不可