センサ付区分開閉器の計測情報を活用したPCSの無効電力制御量の確率的推定手法

書誌事項

タイトル別名
  • A Probabilistic Estimation Method of Reactive Power Controlled by PCS using Measurement Data of Switchgears with Sensors
  • センサ ツキ クブン カイヘイキ ノ ケイソク ジョウホウ オ カツヨウ シタ PCS ノ ムコウ デンリョク セイギョリョウ ノ カクリツテキ スイテイ シュホウ

この論文をさがす

抄録

It becomes an important issue to maintain voltage profile within the allowable range in distribution systems with a large number of distributed generators (DGs), such as Photovoltaic (PV). Although reactive power control by power conditioning system (PCS) is effective to mitigate the voltage increase, there is a possibility that active power curtailment is needed to provide enough amount of reactive power due to current limitation. Here, it is expected that the active power curtailment can be avoided if a cooperative voltage control between load ratio tap controller (LRT) and PCS is realized. To this end, system operators have to know the amount of reactive power controlled by PCS. Hence, in this paper, we developed a new state estimation method of the reactive power using the measurement data obtained by the switchgears with sensors. In addition, a probabilistic approach was applied because an accurate estimation is theoretically impossible only by using the limited number of measurement data. The proposed method was tested in a hierarchic distribution system model and its effectiveness was shown through simulations.

収録刊行物

被引用文献 (2)*注記

もっと見る

参考文献 (13)*注記

もっと見る

詳細情報 詳細情報について

問題の指摘

ページトップへ